Use in IT systems
INFORMATION

EMC limit values
The EMC limit values for interference emission are not specified for voltage supply systems without grounded star point (IT systems). The efficiency of line filters is severely limited.
To ensure IT system capability, the terminal screw shown must be removed from the inverter.
Inverter | Position of the terminal screw |
|---|---|
Size 0S, 0L | See chapter Deactivating the EMC capacitors. |
Sizes 3, 4, 6, 7 | On the right side of the inverter:
|
Size 5 | One screw on the top, another screw on the right side of the inverter:
|
Size 8 | On the right side of the inverter:
|
Additional information