Control command "rapid stop"
Using the rapid stop control command lets you have the frequency inverter brake the motor at the currently applicable rapid stop ramp. The following rapid stop ramps set via parameters basically take effect:
- P136 T13 stop ramp (with active parameter set 1)
- P146 T23 stop ramp (with active parameter set 2)
The process ramp that may have been set via fieldbus does not affect the rapid stop.
This control command is activated by resetting bit 1: Enable/rapid stop.