Switch disconnector

WARNING

Electric shock due to dangerous voltages at the line terminals.
The switch disconnector D01 only disconnects the line voltage at the line terminals X1_b and thus to the connected drive units. Voltage is still present at the line terminals X1_a.
- A correct installation includes that terminals of the device are protected against contact.
NOTICE
Increased wear of the switch contacts.
Destruction of the switch contacts.
- Do not operate the switch disconnector under load.
The switch disconnector of the device serves to interrupt the voltage supply of the connected drive units. The feedback contact of the switch disconnector is evaluated by the controller and can be queried via the device status bit "Maintenance switch position 'OFF'".
The switch disconnector can be secured with 3 locks.