Fault 46 Safety option

Subfault: 46.1

Description: No response from safety option

 

Response: Output stage inhibit

Cause

Measure

No synchronization could be performed with the safety option.

– When using a pluggable safety card, check the device assignment of the basic device and the safety card.

– When using a pluggable safety card, check the slot and installation of the safety card.

– Switch the device off and on again.

– If the fault occurs repeatedly, contact SEW‑EURODRIVE Service.

Subfault: 46.2

Description: Invalid variant

 

Response: Output stage inhibit

Cause

Measure

Safety option variant does not match inverter type.

Use the correct safety option variant.

In the double axis of a MOVIDRIVE® modular application inverter, only safety cards without encoder interface may be used.

Use the correct safety card variant.

Subfault: 46.3

Description: Internal communication timeout

 

Response: Output stage inhibit

Cause

Measure

Communication between inverter and safety option interrupted.

– When using a pluggable safety card, check the installation.

– If the fault occurs repeatedly, contact SEW‑EURODRIVE Service.

Safety option signaled a warning.

– When using a pluggable safety card, check the installation.

– If the fault occurs repeatedly, contact SEW‑EURODRIVE Service.

Subfault: 46.50

Description: Warning

 

Response: Warning with self-reset

Cause

Measure

Safety option signaled a warning

Observe the warning of the safety option subcomponent. Identify the exact cause of this warning and take the appropriate measures for elimination.

Subfault: 46.51

Description: Fault

 

Response: Emergency stop + output stage inhibit with self-reset

Cause

Measure

Safety option detected an error.

Observe the fault code of the safety option subcomponent. Identify the exact cause of this fault message and take the appropriate measures to eliminate the fault.

Subfault: 46.52

Description: System error/critical error

 

Response: Output stage inhibit with self-reset

Cause

Measure

Safety option detected system error or critical error.

Observe the fault code of the safety option subcomponent. Identify the exact cause of this fault message and take the appropriate measures to eliminate the fault.