Fault 48 Module bus
Subfault: 48.1 Description: Incompatible device combination | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Module bus stations are not compatible with one another. | Contact SEW‑EURODRIVE Service. |
Subfault: 48.2 Description: Communication timeout | ||
---|---|---|
| Response: Emergency stop + output stage inhibit | |
Cause | Measure | |
Communication timeout on the module bus. | – Check the cable connections and voltage supply of the module bus stations. – If the fault occurs repeatedly, contact SEW‑EURODRIVE Service. |
Subfault: 48.3 Description: Too many module bus stations | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Too many module stations are connected. | Reduce the number of module bus stations. |
Subfault: 48.4 Description: CRC error | ||
---|---|---|
| Response: Emergency stop + output stage inhibit | |
Cause | Measure | |
Checksum error detected during module bus communication. | – Switch the device off and on again. – Reset the fault. – If the fault occurs repeatedly, contact SEW‑EURODRIVE Service. |