Configuring the fieldbus card

The fieldbus interface for the connection has to be set in the MOVISUITE® project and the device configuration has to be loaded to the MOVI‑C® CONTROLLER via the IEC Editor.

Proceed as follows:

  1. In the configuration of the MOVI-C® CONTROLLER, open the [MOVIRUN® flexible] > [Fieldbus] parameter group.
  2. To integrate the MOVI-C® CONTROLLER as an in the , set "EtherNet/IP™ adapter" as the fieldbus protocol.
  3. To link the EtherNet/IP™ process data interface directly with the MOVIKIT® software module, activate the "Fieldbus interface via IEC modules" parameter.
  4. INFORMATION

    The process data interface is configured in the engineering tool of the PLC (e.g. Studio 5000 Logix Designer). Make sure that the process data module you insert in the hardware configuration at the process data interface (slot) matches the selected MOVIKIT® software module. For example, for MOVIKIT® Velocity, you must insert a process data module of 5 process data words.