Configuring the PROFINET IO controller network
- Adjust the PROFINET and network settings to your requirements in the "General" tab.
- The default setting of the bus cycle task "Use parent's bus cycle settings" is not always the optimal configuration. For the operation of the fieldbus, select an appropriate task from the task configuration or create a new task according to the following example: cyclic task with a call interval of 4 or 10 ms and medium priority
- When planning the application and the task configuration, please note that the processing of the fieldbus stack takes approx. 300 – 400 µs and the execution of the task is blocked for this period.
- Further settings may be required for the respective case of application.