Status LED "BF" (Bus Fault)/"L41"
The status LED "BF" or "L41" is present in the following controllers:
- MOVI-C® CONTROLLER progressive UHX65A‑R (L41)
- MOVI‑C® CONTROLLER advanced UHX45A‑N (BF)
- MOVI‑C® CONTROLLER standard UHX25A‑N (BF)
- MOVI‑C® FIELD CONTROLLER standard MFC1../FHX25‑N (BF)
- MOVI‑C® FIELD CONTROLLER advanced MFC1../FHX45‑N (BF)
The status LED indicates the status of the PROFINET connection. The status LED meets and expands the requirements of AIDA (Automation Initiative of German Domestic Automobile manufacturers).
Status | Possible cause | Measure |
|---|---|---|
Off | Fault-free operating state. The PROFINET device is exchanging data with the PROFINET controller (Data Exchange state). | – |
Red Permanently lit | Connection to the PROFINET controller has failed. Bus communication has been interrupted. | Check the PROFINET connection of the PROFINET device. Check all the cables in the PROFINET network. |
The PROFINET controller is not in operation. | Check the PROFINET controller. | |
The PROFINET device does not detect a PROFINET baud rate. | Check the configuration of the PROFINET controller. | |
Yellow Permanently lit | There is a connection to the PROFINET controller, but the configuration of the PROFINET network is faulty. The following faults may have occurred:
| Check the configuration of the PROFINET controller. |