Startup step
✔
Structure of the MOVISUITE®project
Create a project from a network scan.
Create a project structure in MOVISUITE®.
Startup of components with MOVIRUN® smart
Position the horizontal drive to the left.
Open the "Startup MOVIRUN® smart" configuration menu.
Open the startup assistant of the inverter (X axis).
Configure the drive train.(Do not activate combined encoder evaluation in the drive train)
Add MOVIKIT® StackerCrane MultiMotion.
Activate the "MOVIKIT® MultiAxisController" as "higher-level MOVIKIT®".
Perform optimization DT1.(Determining inertia, configuring stiffness and clearance)
Open the startup assistant of the higher-level software node.
Add the MOVIKIT® StackerCrane MultiAxisController
Configure the control function. (Priority of torque or skew compensation)
Use and configure "Combined encoder evaluation".
Open the startup assistant of the inverter (Y axis).
Add MOVIKIT® StackerCrane effiDRIVE.
Configure the fieldbus interface. (Start address, optional process data, decimal places)
Transfer data to MOVI-C® CONTROLLER.
Saving a MOVISUITE®project
Save the MOVISUITE® project.
Open MOVIRUN® DiagnosticMonitoring.
MAC optimization
Open the IEC Editor via the context menu of the MOVI-C® CONTROLLER.
Perform and save MAC optimization. (Measure time constant, increase P gain of position controller)
Data preservation MOVISUITE®
Compare MOVISUITE® project data with device data.(Function "Devices -> PC" in the context menu of the MOVISUITE®project)