Parameter 100
INFORMATION

Parameter P100 can only be changed if
- All digital inputs are set to "0"
- and DIP switches S1/1 – S1/4 are deactivated by parameter P102
Control setpoint source
- When selecting "Binary", the drive is controlled via the digital input terminals.
- If the mechanical controls f1 and f2 are not deactivated (see parameter P102), the setpoints are specified with setpoint potentiometer f1 and switch f2.
- If the mechanical controls f1 and f2 are deactivated (see parameter P102), the setpoints are specified by selecting setpoints n_f1 or n_f2 (conditions see parameters P160/P161).
- When selecting "RS485", the drive is controlled via the digital input terminals and the bus control word. The setpoint is selected via the system bus.