Group address
Furthermore, ADR = 101 – 115 makes it possible to group several MOVIMOT® inverters. When this is done, all MOVIMOT® inverters in one group are set to the same RS485 address (e.g. group 1: ADR = 1, group 2: ADR = 2).
The master can now specify new group setpoints for these groups with ADR = 101 (setpoints to inverters of group 1) and ADR = 102 (setpoints to group 2). The inverters do not provide a response for this addressing variant. The master must observe a min. rest time of 25 ms between two broadcast or group messages!