Minimum clearance and mounting position
Observe the following information:
- To ensure unobstructed cooling, leave a minimum clearance of 100 mm above and below the device housings. Make sure that the air circulation in this clearance is not impaired by cables or other installation materials.
- Make sure that the regenerative power supply is not subjected to heated exhaust air from other devices.
- Only install the inverters vertically. Do not install them horizontally, tilted, or upside down.
The following specifications must be adhered to for the precharging unit:
- Minimum clearance at the top and bottom: 300 mm
- Minimum clearance on the side: 50 mm
The precharging unit may only be mounted in a suspended position with the connections facing downwards.