Selection of a safety subfunction via safe communication

The response times for the safe communication always relate to the safe protocol and not to the external interface of the safety option. All response times must be multiplied by the factor 1.002.

Calculation factor

Calculation specification response time

STO

T_InputProcessing_F-PO + 2 × T_Sys + 1 ms

SS1-t

T_InputProcessing_F-PO + 2 × T_Sys + SSx‑t delay t1 (8706.8) + 1 ms