Minimum clearance and mounting position

Observe the following information:

  • To ensure unobstructed cooling, leave a minimum clearance of 100 mm above and below the inverter housings. Ensure that the air circulation in this clearance is not impaired by cables or other installation equipment.
  • Make sure that the inverters are not exposed to the exhaust air from other units.
  • Only install the inverters vertically. Do not install them horizontally, tilted or upside down.
  • A lateral clearance of at least 100 mm is only required for size 8. All other devices may be placed directly next to each other.

INFORMATION

Special bending spaces are required according to EN 61800‑5‑1 for cables with a cross section of 10 mm2 and larger. Increase the size of the spaces if necessary.