Analog outputs

NOTICE

Connection of inductive loads to digital outputs.
Destruction of digital outputs.
If inductive loads are connected to digital outputs, you must install an external protective element (e.g. freewheeling diode).

Analog outputs are available when using the I/O option /OAA.

Analog outputs

Number

2

Short-circuit protection

Yes

Voltage output

Tolerance

±5%

Capacitive load

≤ 300 nF

Inductive load

≤ 500 μH

Load resistance

≥ 1 kΩ

Resolution

12 bit

Reset state

0 V

Output value

-10 V to +10 V ≤ 10 mA

Current output

Tolerance

±3%

Capacitive load

≤ 300 nF

Inductive load

None

Load resistance

≤ 500 Ω

Resolution

11 bit

Reset state

0 mA

Measuring range

0(4) – 20 mA

Reference voltage output

Short-circuit protection

Yes

Output voltage

DC -10 V, DC +10 V

Tolerance

±0.5%

Noise

≤ 10 mA

Output current

≤ 3 mA

Capacitive load

≤ 300 nF

Inductive load

≤ 500 μH