Connecting a ground connection or equipotential bonding

[1] | Device | [4] | M5 screw, self-tapping |
[2] | Terminal clip | [5] | HF litz wire (ground strap) |
[3] | Serrated lock washer | [6] | Protective earth (PE) |
Proceed as follows:
- The connection points for the ground connection or equipotential bonding are on the corners of the device [1].
- The connection points are marked with a "ground"
icon.
- Always ground the device using the shortest possible route.
- Push the terminal clip [2] onto the connection point.
- Take an M5 screw [4] and push a serrated lock washer [3], the crimp cable lug for the protective earth [6], or the HF litz wire [5] and another serrated lock washer [3] onto it.
- WARNING! Electric shock due to faulty ground connection or equipotential bonding. Severe or fatal injuries. Tighten the M5 screw [4] with a tightening torque of 4.8 Nm ±4% tolerance using a wrench.