Equipotential bonding
Regardless of the PE connection, it is essential that low-impedance, HF-capable equipotential bonding is provided (see also EN 60204-1 or DIN VDE 0100-540):
- Provide for a connection over a wide area between the device and the mounting plate.
- To do so, use a ground strap (HF litz wire), for example, to connect the device and the grounding point of the system.
- Do not use the cable shields of signal cables for equipotential bonding.
INFORMATION

For detailed information on equipotential bonding for decentralized inverters and drive units, refer to the publication "Drive Engineering – Practical Implementation, EMC in Drive Engineering" in chapter "Equipotential Bonding of Decentralized Inverters" by SEW‑EURODRIVE.
Ensure that there is a HF-capable equipotential bonding for all drive components. Use low-impedance, HF-capable connectors such as HF litz wire or ground straps. Standard protective earth conductors do not achieve sufficient equipotential bonding regarding HF and EMC.

[1] | HF litz wire, ground strap | [4] | Machine base |
[2] | Product | [5] | Cable duct |
[3] | Protective earth (PE) |
|
|