Minimum distances

Observe the following information:

  • To ensure unobstructed cooling, leave a minimum clearance of 100 mm above and below the module housings. Ensure that the air circulation in this clearance is not impaired by cables or other installation equipment.
  • Make sure that the devices are not subjected to heated exhaust air from nearby components.
  • The axis system must be assembled without gaps.

To be able to mount the modules on the DIN rail, minimum clearances are required according to the following figure:

[1]

Locking lever

[2]

DIN rail

[3]

Shield bus carrier (optional)