MOVISAFE® CSB51A characteristic safety values

 

Characteristic values

EN 62061/EN 61800-5-2

EN ISO 13849-1

Tested safety class/standard basis

SIL 3

PL e

Probability of dangerous failure per hour (PFHD value)

5 × 10-9 1/h

Mission time/service life

20 years, after which the component must be replaced with a new one.

Proof test interval

20 years

Safe state

Value "0" for safe F‑DO_STO process value (output disabled).

Safety sub-function

  • STO, SS1-t
  • Safe communication