Safe digital input F-DI
All response times must be multiplied by the factor 1.002.
Calculation factor (formula symbol) | Calculation specification response time |
---|---|
Input processing time with F-DI selection (T_InputProcessing_F-DI) | Input filter time (8704.2) + 2 ms + T_Sys + 350 µs |
Input processing with F-DI deselection: (T_InputProcessing_F-DI_Deselection) | |
| Input filter time (8704.2) + 51 ms + T_Sys + 350 µs |
| Input filter time (8704.2) + 2 ms + T_Sys + 350 µs |
Response time of line diagnostics | 30 ms (the response times of the safety sub-functions are not taken into consideration) |