Minimum clearance and mounting position
Observe the following information:
- To ensure unobstructed cooling, leave a minimum clearance of 100 mm above and below the inverter housings. Make sure air circulation in the clearance is not impaired by cables or other installation equipment.
- Make sure that the inverters are not exposed to the exhaust air from other units.
- Only install the inverters vertically. Do not install them horizontally, tilted or upside down.
- Clearance at the side is not necessary. The units are allowed to be arranged directly next to one another.