Minimum clearance and mounting position

Observe the following information:

  • To ensure unobstructed cooling, leave a minimum clearance of 100 mm above and below the inverter housings. Make sure air circulation in the clearance is not impaired by cables or other installation equipment.
  • Make sure that the inverters are not exposed to the exhaust air from other units.
  • Only install the inverters vertically. Do not install them horizontally, tilted or upside down.
  • Clearance at the side is not necessary. The units are allowed to be arranged directly next to one another.

INFORMATION

Special bending spaces are required according to EN 61800‑5‑1 for cables with a cross section of 10 mm2 and larger. Increase the size of the spaces if necessary.