Terminal assignment MGF..1-DSM-C/DI

Observe the wiring instructions in the documentation of the frequency inverter that you use.

Attach units without a plug connector to the terminals as follows:

  1. WARNING! Electric shock caused by dangerous voltages in the connection box. Severe or fatal injuries. De-energize the device. Pay attention to the 5 safety rules in chapter “Carrying out electrical work safely”.
  2. Secure the output shaft of permanently excited motors against rotation. You thereby avoid an electric shock from the regenerative operation during the rotation of the shaft.
  3. Loosen the screws of the cover. Remove the cover.
  4. Route the cables through the cable glands into the connection box.
  5. For designs with UL, plug in plug connector X16_A as follows:
    • Loosen the screw [1]. Remove the cover of the plug connector.
    • Plug in the X16_A plug connector.
    • Reinstall the cover of the plug connector.
  6. Connect the unit in accordance with the following terminal assignment.

The following figure shows the terminals of MOVIGEAR® MGF..1-DSM-C/DI:

Terminal

Name

Function

X2_A
terminals for motor connection

W

Phase W

V

Phase V

U

Phase U

PE

PE connection

X16_A DDI interface

DDI

MOVILINK® DDI interface