Process output data

The following table shows the process output data from the PLC to the inverter for control via fieldbus with 8 process data words.

INFORMATION

The "V/P" column indicates whether the respective process data word or bit is only available when using MOVIKIT® Positioning Drive (P) or whether it is also available when using MOVIKIT® Velocity Drive (V/P).

Word

Bit

V/P

Function

PO 1

Control word

0

V/P

Enable/emergency stop

1

V/P

Enable/application stop

2

V/P

Reserved

3

V/P

Release brake (without enable)

4

P

Jog positive

5

P

Jog negative

6

P

Apply relative position

7

V/P

Start/stop with fieldbus ramp

8

V/P

Fault reset

9

V/P

Reserved

10

V/P

Activate drive train 2

11

V/P

Reserved

12

P

Disable software limit switches

13

V/P

Activate output stage inhibit

14

V/P

Activate standby mode

15

V/P

MOVIKIT® Handshake In

PO 2

Setpoint speed

0 – 15

V/P

User unit

PO 3

Setpoint acceleration

0 – 15

V/P

User unit

PO 4

Setpoint deceleration

0 – 15

V/P

User unit

PO 5

Digital outputs

For control via process data (see Digital inputs/outputs)

0

V/P

DO 00 / DIO 01 (output)

1

V/P

DO 01 / DIO 02 (output)

...

V/P

...

3

V/P

DO 03

...

V/P

...

PO 6

Target application mode

0 – 15

P

Operating mode (see Operating modes)

PO 7

High word target position

0 – 15

P

User unit

PO 8

Low word target position

0 – 15

P

User unit