Permitted terminal tightening torques

  1. NOTICE! Failure to adhere to prescribed tightening torques. Damage to the device. Connect the power cables with the specified tightening torques.

Observe the following information:

  • Always tighten the terminals or terminal studs by hand and not with electrically or pneumatically operated tools.
  • Adhere to the specified tightening torques with a tolerance of +/- 10%.

Tightening torques in Nm

Line connection

X1

0.6

Motor and braking resistor connection

X2

0.6

Terminal screw for TN/IT systems

EMC

2.5

Other screw connections

–

1.5