Parameter 170 – 173
Fixed setpoint n0 – n3
The fixed setpoints n0 – n3 are valid if parameter P600 terminal configuration at "1" = terminal configuration 2 (selection of fixed setpoints).
You can then select fixed setpoints n0 – n3 using the programmed functionality of the input terminals.
The sign of the fixed setpoint determines the direction of rotation of the motor.
|
Parameter |
Active setpoint |
Status Terminal L |
Status Terminal f1/f2 X6:7,8 |
|---|---|---|---|
|
P170 |
n0 |
OFF |
OFF |
|
P171 |
n1 |
ON |
OFF |
|
P172 |
n2 |
OFF |
ON |
|
P173 |
n3 |
ON |
ON |
X6:9,10