b) Receive response message

(Acknowledgment signal + actual values from MOVIMOT® inverter)

  1. The response message must be received within approx. 100 ms, otherwise, for example, it is sent again.
  2. Calculated block check character (BCC) of response telegram = received BCC?
  3. Start delimiter of response telegram = 1Dhex?
  4. Response address = Request address?
  5. Response PDU type = Request PDU type?
  6. All criteria met: => Transfer OK! Process data valid!
  7. The next request message can now be sent (continue from point a).

All criteria met: => Transfer OK! Process data valid! The next request message can now be sent (continue from point a).