Functional description

The current limit can be set on switch f2.

The setpoint f2 (for binary control) and the minimum frequency (with control via RS485) are permanently set to the following values:

Setpoint f2:

5 Hz

Minimum frequency:

2 Hz

The monitoring function comes into effect above 15 Hz. If the drive operates at the current limit for longer than 500 ms, the unit generates an error (error 44). This is indicated by the status LED flashing red quickly.