Useful life
The storage units are subject to aging due to environmental effects and operating conditions. This leads to a decrease in the useful capacitance and an increase in the equivalent series resistance of the storage units.
This means that the storage units have a limited useful life. The end of the useful life is defined as the point in time when one or both of the following cases occur:
- The capacitance of the energy modules is reduced by 20%.
- The equivalent series resistance of the energy modules has increased by 100%.
INFORMATION