Connection when using a hybrid cable
Observe the following information:
- For the shield connection, use the designated shield plates on the axis module.
- Apply the shielding of the hybrid cable over the entire circumference over a large area.
- Keep the distance or cable length between the shield connection and the connection for the cable conductors as short as possible.
- To avoid communication errors, the exposed length of the coaxial cable must not exceed 50 cm. For more information, refer to the addendum to the "Digital Motor Integration MOVILINK® DDI Toolset 1" operating instructions.