Installing the line filter

Observe the following information:

  • Install the line filter close to the power supply module but outside the minimum clearance for cooling. The line filter must not be heated by the exhaust air of the power supply module.
  • Mount the line filter and power supply module on a shared mounting plate. Make sure they are connected over as large an area as possible and with good conductivity.
  • Observe the following minimum distances and mounting positions for convection cooling:

Permitted mounting position

Distance in mm

On the side

Downward

Upward

3 and 4

0

100

100

  • Observe the following permitted mounting positions during installation: