Fault 6 Line fault

Subfault: 6.1

Description: Line phase failure

 

Response: Line phase failure

Cause

Measure

Missing line phase detected.

Check the supply system cable.

DC link voltage periodically too low.

Check the configuration of the supply system.

Inadequate line voltage quality.

Check the supply (fuses, contactor).

Subfault: 6.2

Description: Power failure

 

Response: Power failure

Cause

Measure

Power failure detected.

Check the supply system cable.

Subfault: 6.3

Description: Line overvoltage

 

Response: Emergency stop + output stage inhibit

Cause

Measure

Line voltage exceeds permitted upper threshold value.

Check the nominal line voltage used in the project planning.

Inadequate line voltage quality.

Check the quality of the power system.

Subfault: 6.4

Description: Line undervoltage

 

Response: Line undervoltage

Cause

Measure

Line voltage dropped below permitted lower threshold value.

Check the nominal line voltage used in the project planning.

Inadequate line voltage quality.

Check the quality of the power system.

Supply system cable missing.

Check the wiring.