Additional process values of the inverter on the fieldbus

Additional process values of the inverter can be placed on the fieldbus using the "Optional process data". If a MOVIKIT® MultiAxisController is cascaded in the project, the first cascaded axis is output in each case.

Do the following to configure the additional process values of the inverter to the fieldbus:

  1. In the configuration of the MOVIKIT® StackerCrane MultiMotion of an axis subordinate to the software module, activate the additional function "Additional process values of the inverter" in the "Module configuration" > "Basic settings" configuration menu and select the number of additional process values.
    • In the configuration of the MOVIKIT® StackerCrane MultiMotion, the "Additional functions" > "Additional process values of the inverter" configuration menu is displayed.
  2. In the configuration of the MOVIKIT® StackerCrane MultiMotion, configure the function of the required additional process values in the "Additional functions" > "Additional process values of the inverter" configuration menu.
  3. In the configuration of the MOVIKIT® StackerCrane, activate the created additional process values in the "Module configuration" > "Optional process data" configuration menu.