Fault 7 DC link

Error: 7.11 (070Bhex | 1803dec)

Description: DC link overvoltage at rectifier

 

Response: Remote – critical fault with self-reset

Cause

Measure

The fault can be caused as follows:

– The maximum permitted DC link voltage limit of the rectifier was exceeded.

– The AC voltage component of the DC link voltage is too high.

– Check the system and nearby devices for ground faults.

– Check the quality of the supply system (line voltage distortion).

– Check line voltage