Fault 7 DC link
Error: 7.11 (070Bhex | 1803dec) Description: DC link overvoltage at rectifier | ||
---|---|---|
| Response: Remote – critical fault with self-reset | |
Cause | Measure | |
The fault can be caused as follows: – The maximum permitted DC link voltage limit of the rectifier was exceeded. – The AC voltage component of the DC link voltage is too high. | – Check the system and nearby devices for ground faults. – Check the quality of the supply system (line voltage distortion). – Check line voltage |