Fault 34 Process data configuration
Error: 34.1 (2201hex | 8705dec) Description: Changed process data configuration | ||
|---|---|---|
| Response: Warning | |
Cause | Measure | |
Process data configuration changed during active process data operation. | Perform a reset. Doing so will stop the process data, apply the changes, and restart the process data. | |
Error: 34.2 (2202hex | 8706dec) Description: Invalid process data configuration | ||
|---|---|---|
| Response: Warning with self-reset | |
Cause | Measure | |
An invalid process data configuration has been set on the controller. | – Select a valid process data configuration. – Set the quantity of process data according to the product manual. | |
Error: 34.3 (2203hex | 8707dec) Description: Number of configured process data too low | ||
|---|---|---|
| Response: Warning with self-reset | |
Cause | Measure | |
Too few process data is transferred from the controller. | – Select a valid process data configuration. – Reduce the number of axes connected to the gateway. | |
Error: 34.4 (2204hex | 8708dec) Description: Number of configured process data too high | ||
|---|---|---|
| Response: Warning with self-reset | |
Cause | Measure | |
Too much process data is transferred from the controller. | – Select a valid process data configuration. – Increase the number of axes connected to the gateway. | |