Inverter-related earth-leakage currents
Earth-leakage currents of ≥ 3.5 mA can occur during normal operation.
Earth leakage currents are mainly determined by:
- The amount of DC link voltage
- The PWM frequency
- The motor cable used and its length
- The motor used
Reducing earth-leakage currents (size 0 only)
You can deactivate the suppression capacitors to PE (see chapter "Installation / operation on IT systems") to reduce earth-leakage currents in the inverter.
When the suppression capacitors are deactivated, the EMC filter is no longer active.
SEW-EURODRIVE recommends that you do not use earth-leakage circuit breakers and instead choose other measures to ensure protection of personnel (e.g. according to EN 61800-5-1, EN 50178, EN 60204-1, etc.).