| | → | Clarification of - Technical data and requirements
- Basic conditions
- System interfacing
|
| |
| | |
| | | ↓ |
| | | Calculation of the relevant application data - Stationary, dynamic, regenerative power
- Speeds
|
| | | ↓ |
| | | Gear unit selection Determine - gear unit version, gear unit size, gear
unit reduction ratio
Check for
gear unit utilization (Mamax ≥
Ma(t)) |
| | | ↓ |
| | → | Motor selection - Convert torque and speed for the motor
shaft
- Define the motor
|
| |
| | |
| | | ↓ |
| | ← | Check - Max. torque which can occur Mmax < 1.5 × MN
- Required motor speed < nN
- Thermal load by taking into account setting range and cyclic
duration factor
|
| |
| | |
| | | ↓ |
| | | Selecting the MOVITRAC® B
frequency inverter - Motor/inverter
assignment
- Continuous power, peak power
- Installation conditions
- FBG11B keypad option
- DBG60B plain text keypad option
- FSC11B/21B communication option
- FIO11B analog module option
- FIO21B digital module option
- EtherCAT® FSE24B option
- UWS11A / UWS21B / USB11A interface adapter option
|
| | | ↓ |
| | | Selecting the braking resistor - Based on the calculated regenerative power
and the cyclic duration factor
|
| | | ↓ |
| | | Compilation of components - Line choke, output choke, touch guard
|
| | | ↓ |
| | ← | Check whether all requirements
have been met. |
| |