Reference signal

With this parameter, you can program a reference signal with regard to the actual value of the PI controller. By doing this, you can monitor the actual value for violation of a limit value.

P450

– 100%

Step width:

0.1%

P451

Signal = "1" if:

PI actual value < PI reference

PI actual value > PI reference

You have to program a digital output terminal to "PI controller actual value reference" to issue the reference signal. The reference signal operates with a hysteresis of 5%. The reference signal does not have a delay time and signals "1" depending on P451.

You must program the digital output DO01 P620, DO02 P621 or DO03 P622 to PI controller actual value reference.