Speed-torque characteristic curve
The speed-torque characteristic curve looks as follows:
244146315 |
[1] M in S1 100% cdf [2] P in S1 100% cdf |
Characteristic curve 1:
Below 20 Hz, the drive cannot be loaded with the rated motor torque. The reduced speed decreases the self-cooling of the motor. As a result, the motor would heat up excessively.
This limit is not caused by the inverter. Motors with sufficient forced cooling can even be loaded with a nominal torque below 20 Hz.