Enabling the network

The SP master manages the enable control of the network. If the SP master receives the enable signal, all the synchronization stations switch from the status "Output stage inhibited" to the status "Output stage enabled".

The prerequisite for this is that there is no fault and each station reports the status "no enable".

INFORMATION

Compare the process values of the SP slaves with the process values of the SP master. Usual differences in output voltages are less than 40 V. Usual differences in active power are less than 10% of the nominal device power. Contact SEW‑EURODRIVE if you have any questions.