Assembly instructions

The following requirements apply to the connection leads:

  • Single conductors can be used for the digital I/O connections.
  • If the I/O cables are longer than 1 m, install them with shielding.
  • Connect the stepper motor and encoder using shielded cables.
  • If the length is more than 1 m, shield the motor power supply cable.
  • Route shielded cables directly below the module on the shield bus provided for this purpose:
    • Connect the shield bus to the base plate using a local, low-impedance connection.
    • Connect the shields of the external cables to earth/ground at the entrance to the control cabinet.

INFORMATION

Improper shielding can lead to increased electromagnetic radiation. Please note the information in the Electrical installation chapter.