Fault 6 Line fault

Error: 6.1 (0601hex | 1537dec)

Description: Line phase failure

 

Response: Line phase failure

Cause

Measure

Line phase missing.

Check the supply system cable.

Poor line voltage quality.

Check the supply (fuses, contactor, line components).

DC link voltage periodically too low.

Check line voltage.