Minimum clearance and mounting position

When installing the inverters in the control cabinet, observe the following:

  • To ensure unobstructed cooling, leave a minimum clearance of 100 mm above and below the inverter housings. Ensure that the air circulation in this clearance is not impaired by cables or other installation equipment.
  • Make sure that the inverters are not within the area of the warm exhaust air of other devices.
  • Install the inverters only vertically. Do not install them horizontally, tilted or upside down.
  • Clearance at the side is not necessary. The units can be arranged directly next to one another.

INFORMATION

Special bending spaces are required according to EN 61800‑5‑1 for cables with a cross section of 10 mm2 and larger. This means the clearance must be increased if required.