Minimum clearance and mounting position
When installing the inverters in the control cabinet, observe the following:
- To ensure unobstructed cooling, leave a minimum clearance of 100 mm above and below the inverter housings. Ensure that the air circulation in this clearance is not impaired by cables or other installation equipment.
- Make sure that the inverters are not within the area of the warm exhaust air of other devices.
- Install the inverters only vertically. Do not install them horizontally, tilted or upside down.
- Clearance at the side is not necessary. The units can be arranged directly next to one another.