NF.. line filter

Observe the following information:

  • Do not wire any other consumers between the line filter and the device.
  • No switching is allowed between the line filter and the device.
  • The connection cable between the line filter and the device does not have to be shielded.
  • Limit the length of the cable between the line filter and the device to the required length.
  • Always lay the cables before and after the line filter separately.
  • Under no circumstances should the cables before and after the line filter be routed along the motor cable.