F-communication when activated
The F-communication when activated parameter defines the behavior of safe communication with the higher-level safety controller when the prioritized terminal control is activated.
Parameter | Setting | Meaning |
|---|---|---|
F-communication when activated | Yes | Safe communication is interrupted when the prioritized terminal control is activated. The signals of the higher-level safety controller are no longer active on the inverter. This causes the safety card to signal a safe communication timeout error and the safety sub-functions are activated.
The "Muting F-PO" function can be used to deactivate the safety sub-functions and thus enable the drive again. |
No | Safe communication is not interrupted when the prioritized terminal control is activated. The signals of the higher-level safety controller are still active on the inverter. |