Fault 17 Internal processor error
Fault: 17.7 (1107hex | 4359dec) Description: Exception error | ||
|---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Internal trap in CPU. | – Switch the device off and on again. – If the fault occurs repeatedly, contact SEW-EURODRIVE Service. | |
Fault: 17.8 (1108hex | 4360dec) Description: Non-volatile data not loaded | ||
|---|---|---|
| Response: Output stage inhibit System state: Fault acknowledgement with CPU reset | |
Cause | Measure | |
The CPU was restarted several times without the firmware being fully initialized. Non-volatile data is not loaded and the default values remain active. | – Acknowledge the error. – Check the voltage supply. – If the error occurs repeatedly, contact SEW-EURODRIVE Service. | |