Fault 32 Communication
Subfault: 32.2 Description: EtherCAT®/SBusPLUS process data timeout | ||
|---|---|---|
| Response: Fieldbus – timeout response | |
Cause | Measure | |
Timeout in process data transfer during EtherCAT®/SBusPLUS communication. | – Check the wiring of the system bus and module bus. – Check that the EtherCAT®/SBusPLUS configuration is set correctly in the MOVI-C® CONTROLLER. – Check the EtherCAT®/SBusPLUS timeout configuration in the device. | |
Subfault: 32.3 Description: Faulty synchronization signal | ||
|---|---|---|
| Response: Warning + line contactor unchanged + module bus response "Warning" with self-reset | |
Cause | Measure | |
Faulty synchronization signal period. | Check for correct setting of the EtherCAT®/SBusPLUS configuration in the MOVI-C® CONTROLLER. | |
Subfault: 32.4 Description: No synchronization signal | ||
|---|---|---|
| Response: Warning + line contactor unchanged + module bus response "Warning" with self-reset | |
Cause | Measure | |
No synchronization signal present. | Check for correct setting of the EtherCAT®/SBusPLUS configuration in the MOVI-C® CONTROLLER. | |
Subfault: 32.5 Description: Synchronization timeout | ||
|---|---|---|
| Response: Warning + line contactor unchanged + module bus response "Warning" with self-reset | |
Cause | Measure | |
Timeout while synchronizing to synchronization signal. | Check for correct setting of the EtherCAT®/SBusPLUS configuration in the MOVI-C® CONTROLLER. | |
Subfault: 32.6 Description: Copy parameter set | ||
|---|---|---|
| Response: Output stage inhibit + line contactor unchanged + module bus response "Critical" | |
Cause | Measure | |
Error while downloading parameter set to device. | – Check the wiring of the system bus and module bus. – Restart download. | |
Subfault: 32.7 Description: Application heartbeat timeout | ||
|---|---|---|
| Response: Application heartbeat – timeout response | |
Cause | Measure | |
Communication interrupted between IEC program in MOVI-C® CONTROLLER and device. | – Check the status of the IEC program. – Restart the IEC program. | |