Fault 7 DC link

Subfault: 7.1

Description: DC link overvoltage

 

Response: Output stage inhibit + line contactor unchanged + module bus response "Critical"

Cause

Measure

Maximum permitted DC link voltage limit exceeded and output stage inhibited by hardware.

– Extend the deceleration ramps.

– Check the supply cable to the braking resistor.

– Check the technical data of the braking resistor.

Subfault: 7.4

Description: DC link undervoltage

 

Response: Output stage inhibit + open line contactor + module bus response "Critical"

Cause

Measure

DC link voltage exceeded lower limit and output stage inhibited by hardware.

– Reduce the dynamic load change from regenerative operation to motoring operation.

– Check previous error, e.g. line phase failure or supply system off in motor mode.

Subfault: 7.9

Description: Short circuit

 

Response: Output stage inhibit + open line contactor + module bus response "Critical"

Cause

Measure

Short circuit in the DC link.

Check the DC link busbar.

Subfault: 7.10

Description: Precharging timeout

 

Response: Output stage inhibit + open line contactor + module bus response "Critical"

Cause

Measure

Capacitive load too high in the DC link.

Check the project planning.