Process sequence and signal states
INFORMATION

For the behavior of the drive in idle state, observe the information for the "Stop functions" in the "Functions" > "Monitoring functions" > "Control functions" configuration menu of the inverter.
No. | Process | PD | Signal states |
|---|---|---|---|
[1] General enable |
| PO 1:0 |
|
| PO 1:1 |
| |
[1] | Selection of operating modes "Cut length control without material sensor" | PO 6 | 1400 (decimal) |
[1] to [2] | Start of the axis | PO 1:7 PO 18/19 PI 2 |
|
Instant cut | PO 9:0 |
| |
[1] to [5] | ACTIVE | PI 9:0 |
|
[2] | Drive is synchronous | PI 9:1 |
|
[3] | Start "Pulling a gap" | PO 9:2 |
|
[3] to [4] | "Pulling a gap" active |
| The drive superimposes a travel profile to generate a gap in the material. |
[4] | "Pulling a gap" finished | PI 9:2 |
|
[4] to [5] | Move to start position | PO 9:1 PO 7/8 |
|
[5] | If the actual position lies within the configured window width, the feedback "In position" is issued. The drive stops subject to position control. | PI 1:7 |
|
Behavior when enable is withdrawn:
If the enable is withdrawn from the drive while the synchronous operation status is not equal to "STOPPED", the drive stops with the corresponding deceleration and the operating mode is canceled.
The drive must be moved back to the start position using the "Positioning absolute" operating mode (400) before the "Automatic – cut length control" operating mode (1400) can be started again.
If the enable is withdrawn from the drive while the synchronous operation status is "STOPPED", the drive is stopped. A new enable continues the movement. If the synchronization position has not yet been reached, the drive synchronizes again after the cutting length has been reached. Otherwise, an error is reported.
Behavior when start is withdrawn:
If the start signal is withdrawn from the operating mode while the synchronous operation status is not equal to "STOPPED", the drive desynchronizes according to the configured desynchronization strategy and the operating mode is canceled.
The drive must be moved back to the start position using the "Positioning absolute" operating mode (400) before the "Automatic – cut length control" operating mode (1400) can be started again. If the start signal is withdrawn from the operating mode while the synchronous operation status is "STOPPED", the drive is stopped with the deceleration PO 4. When the start signal is present again, the operating mode is continued. If the target cutting length has not yet been reached, the drive synchronizes again after the cutting length has been reached. Otherwise, an error is reported.