MOVISAFE® CSB/CSL characteristic safety values

 

Characteristic values

EN 62061/IEC 61800-5-2

EN ISO 13849-1

Tested safety class/standard basis

SIL 2

PL d

Probability of dangerous failure per hour (PFHD value)

7 × 10-9 1/h

Mission time/service life

20 years, after which the component must be replaced with a new one.

Proof test interval

20 years

Safe state

Value "0" for all safe F-DO process values (output disabled)

Safety sub-function

  • STO, SS1, SLS, SSM, SDI, SBC
  • Safe digital inputs/outputs
  • Safe communication