Control functions
INFORMATION

The configuration parameters only take effect for the master source "configured axis".
Parameter designation | Description |
|---|---|
Master stop if slave fault occurs | |
Master stop if slave fault occurs | Activation of slave monitoring for a master axis
|
Index: 50040.50 | |
IEC name: – | |
Master stop fault response |
|
Index: 50040.51 | |
IEC name: – | |
Application heartbeat | |
Timeout | If communication between the MOVI-C® CONTROLLER and the lower-level members is interrupted for the set time, the members stop with the specified fault response. The fault response is defined in the member under [Functions] > [Monitoring functions] > [Overview of fault responses] in the parameter "Response timeout application heartbeat" (index 8622.21) and executed at a timeout time of greater than 0. Default value: 0.2 s |
Index: 8330.3 | |
IEC name: – | |
Response to application heartbeat timeout | Fault response to the application heartbeat timeout. Is executed if the timeout time is exceeded and configured to greater than 0. Default value: Application stop + output stage inhibit |
Index: 8622.21 | |
IEC name: – | |