Control functions

INFORMATION

The configuration parameters only take effect for the master source "configured axis".

Parameter designation

Description

Master stop if slave fault occurs

Master stop if slave fault occurs

Activation of slave monitoring for a master axis

  • Off
  • No response by the master axis during a slave fault
  • On
  • Master axis is stopped or does not start at all if one of the slave axes reports a fault or is not in "FCB 10 Interpolated position control". The master axis remains in the selected operating mode and is stopped via the ramp set under "Master stop fault response".

Index: 50040.50

IEC name:

Master stop fault response

  • Application stop
  • If one of the slave axes reports a fault or is not in "FCB 10 Interpolated position control", the axis is stopped via the application limit "Deceleration".
  • Emergency stop
  • If one of the slave axes reports a fault or is not in "FCB 10 Interpolated position control", the axis is stopped with the emergency stop deceleration.

Index: 50040.51

IEC name:

Application heartbeat

Timeout

If communication between the MOVI-C® CONTROLLER and the lower-level members is interrupted for the set time, the members stop with the specified fault response. The fault response is defined in the member under [Functions] > [Monitoring functions] > [Overview of fault responses] in the parameter "Response timeout application heartbeat" (index 8622.21) and executed at a timeout time of greater than 0.

Default value: 0.2 s

Index: 8330.3

IEC name:

Response to application heartbeat timeout

Fault response to the application heartbeat timeout. Is executed if the timeout time is exceeded and configured to greater than 0.

Default value: Application stop + output stage inhibit

Index: 8622.21

IEC name: